STEP5 / UNITY path general information
This chapter gives the general informations for STEP5 to UNITY conversion path.
Variable translation schemes
The comments of the variables are kept with their initial values (only for DB variables) but not the name.
There are two types of variables: The Memento variables The data block variables
Mementos variables
| @S5 | Unity Name | Unity Type | @ Unity | Example |
|---|---|---|---|---|
| Mx.y | Mx_y | BOOL | %MW(x/2).y | M10.0 ⇒ %MW5.0 |
| MBx | Mbx | BYTE | %MW(x/2) | MB20 ⇒ %MW10 |
| MWX | Mwx | INT | %MW(x/2) | MW30 ⇒ %MW15 |
Data block variables
| S5 DB Number | S5 DB WORD Number | Unity Name | Unity Type | @ Unity |
|---|---|---|---|---|
| DBx | Wy | Dbx_Wy | INT | Memory plan DB begin at %MW6000 |
Input/Output
The mapping of the digital inputs/outputs of the source must be done by the user to define the new location in the new hardware configuration.
| @S5 | Unity Name | Unity Type | @ Unity |
|---|---|---|---|
| Ex.y | Ex_y | EBOOL | user define |
| Ax.y | Ax_y | EBOOL | user define |
| EBx | EBx | BYTE | user define |
| EWx | EWx | INT | user define |
| ABx | ABx | BYTE | user define |
| AWx | AWx | INT | user define |
Codes modules translation schemes
Module name (OB, PB, SB,etc.) is converted like comment at the beginning of the section or SR.
Segment name and segment number are converted like comments at the beginning of the segment.
Language
The original Step5 code is always LIST. After translation in UNITY, by default the generated code is LADDER. But if some errors occur during the translation, the generated code is literal.
OB : Organization Block
OBs are translated in section and named Mast_Obx where x is the OB number.
<note> some OB may be translated as SR. </note>
PB : Program Block
PBs are translated in subroutine (SR)and named Mast_Pbx where x is the PB number.
SB : Sequential Block
SBs are translated in subroutine (SR)and named Mast_Sbx where x is the SB number.
FB / FX : Functions Block
FBs or FXs are translated in subroutine (SR) and named Mast_Fbx or Mast_FXx where x is the FB/FX number.
The Comments of the program
Only the comment of the last instruction is kept.
This Step5 code
0013 :U E50.4 px tappo ext 0014 :UN M96.2 controllo tappo fatto 0015 :S M111.4 ev contr tappo
is translated in UNITY by
if E50_4 and not M96_2 then (* ev contr tappo*) Set (M111_4); end_if;
The System functions
Timers
Each Step5 timer type is translated by DBF S5_timer, whose behavior is the same as Step5 timer.
| Step5 Timer Type | DFB input Timer_type |
|---|---|
| SI | 1 |
| SE | 2 |
| SV | 3 |
| SS | 4 |
| SA | 5 |
| Reset | 7 |
Counters
The ZV and ZR counters are translated by an integer.
| S5 Counter | UNITY |
|---|---|
| ZVx | Zvx_Val_Int |
| ZRx | Zrx_Val_Int |
Zvx_Val_Int is incremented on the rising edge of the condition.
Zrx_Val_Int is decremented on the rising edge of the condition.
The constructor FB
The constructor FB are not translated. The user has to translate them manually.
The Special functions
The special functions ( communications, regulation, axes, motion, …) are not translated. The user has to translate them manually.
intrinsic limitations of the conversion
Memory Access by absolute addresses
All memory access instructions by the absolute address are not supported.
Examples : instructions TIR, LIR, TNB, TNW,…
Indexation
In Step5, indexation instructions are identified by the character “B” followed by the address of the index (MW16 in the below example).
003A :B MW16
Only indexation instructions on a DB word are translated.
002B :L MW26 002C :B MW16 002D :T DW0
is well translated by
Dbx_w0_ar[MW16] := MW26;
All other indexation instructions on Mementos, DB, FB, conditional jump… are not translated.
- example of unsupported indexation when calling a DB:
002C :B MW16 002D :A DB10
it affects all following usages of DWx that refer to that selected DB which is unknown because indexed by the value of MW16.
- example of unsupported indexation for affectation of analog outputs:
0015 :L DW0 0016 :B MW196 0017 :T AW0
here the problem is that indexation on outputs are not supported by Unity-Pro.
- example of unsupported indexation for conditional jump:
<note> In the example bellow, the execution of one of the jumps (SPA instr.) to label Lxxx depends on the value of the index at address MW128. The user has to translate them manually.
011C :B MW128 011D :SPA L129 011E :SPA L12B 011F :SPA L130 0120 :SPA L135 0121 :SPA L13A 0122 :SPA L13C 0123 :SPA L148 0124 :SPA L149 0125 :SPA L14A 0126 :SPA L14B 0127 :SPA L14C
</note>
Overlapping mementos address (bit, byte, word)
Step5 Memory Mapping Coding in little endian
| WORDn+1 | ||||||||||||||||||||||||||||||||
| WORDn | WORDn+2 | |||||||||||||||||||||||||||||||
| BYTEn | BYTEn+1 | BYTEn+2 | BYTEn+3 | |||||||||||||||||||||||||||||
| 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | |
Unity Memory Mapping Coding in big endian
| WORDn | WORDn+1 | |||||||||||||||||||||||||||||||
| BYTEn | BYTEn+1 | |||||||||||||||||||||||||||||||
| 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |
Bytes are addressed in word (%MW)
if in same S5 code, you have two consecutive words (for example MW0 and MW1), when you write byte MB1, you write also MW0 and MW1.
the user must identify in the code:
- overlapping of bits, bytes and words
- Consecutive words eg (MW10, MW11, MW12 …)
and adapt the code accordingly
What is the current DB
In some cases, it is difficult to determine the current DB.
For example here we first use the DB10 (“A DB10”) before calling FB10 (“SPA FB10”)
0001 :A DB10 0002 :SPA FB10
and at the beginning of FB10, depending on the value of M10.0 (“U M10.0”) we either jump to L000 (“SPB L000”) or continue and use the DB20 (“A DB20”) and just before the L000 label (“L000:”) we use the DB30 (“A DB30”).
0100 :U M10.0 0101 :SPB L000 0102 :A DB20 ...... ...... ...... 0120 :A DB30 0121 L000:L MW22 0122 :T DW11
In this case, current DB depends on the value of M10.0. In line 0122, current DB is DB10 if M10.0 is TRUE else DB current is DB30.
But the translation is:
DB30_w11 := MW22;
The user must identify these problems and rewrite the translated code.