606 - more than one interpretation

Message: “At {location}, there could be more than one interpretation for {code}”

Example: “At <orphee_cc>: 738-7, there could be more than one interpretation for N_INSTR_APPEL_PROC: 26160: bfc_shrz”

It is not possible to determine the effective function/procedure/variable/… because there could be more than one interpretation.

It is often an issue of missing parameters in the procedure call.

For example when translating an Orphee bfc_shrz to Schneider Unity-Pro, the following call can not be determined because the type of formal parameter, “rest”, is unknown:

      bfc_shrz(, id_30, int(12), li1, md_26848);

In this case, the type of parameter “rest” can be Int or Dint, and it is nonderterministic.

The problem can here be resolved by creating a local variable in the Glips file in order to force the use of the procedure that has a “rest” parameter of type dint:

      declare
        li1 : bool;
        rest : dint;
      begin
...
      bfc_shrz(, id_30, int(12), li1, md_26848, rest);