50001 - Special instructions of the TSX with parameters unsupported by the PLC Converter
Message: “At {location}, Smart instruction '{npcall}', with parameters '{param}', is not supported.”
Example: “At MAST-SR3-L:3,C:6, Smart instruction 'REXREG', with parameters '( 7, 5, 20962, 20960, 35398)', is not supported.”
Explanation: A function is used with unsupported parameters.
DMASKINT
Unmask the interruption of a coupler.
DmaskInt is not supported by PLC Converter
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| IT | non convertible | SPECI_TSX7 | NC |
READREG
Immediate and asynchronous reading of register of a Coupler
ReadReg is not supported by PLC Converter
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
WRITEREG
Immediate and asynchronous writing of register of a Coupler
WriteReg is not supported by PLC Converter
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
READINT
Test the interruption of a coupler.
ReadInt is not supported by PLC Converter
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| IT | non convertible | SPECI_TSX7 | NC |
ACKINT
Acknowledge the interruption of a coupler.
AckInt is not supported by PLC Converter
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| IT | non convertible | SPECI_TSX7 | NC |
READBIT
Immediate and asynchronous reading of the value of a digital input.
This function is not supported by PLC Converter.
The code must be manually adapted taking in account that the asynchronous reading of input is not supported.
Please note that the durations of actual PLC cycle time are shorter than those of the TSX.
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
WRITEBIT
Immediate and asynchronous writing of the value of a digital output of a module. This function is not recognize by the TSX analyzer.
The code must be manually adapted taking in account that the asynchronous writing of output is not supported.
Please note that the durations of actual PLC cycle time are shorter than those of the TSX.
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
RTOR
see READBIT.
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
WTOR
see WRITEBIT.
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | non convertible | SPECI_TSX7 | NC |
REXREG
read extended register is not supported by PLC Converter
This function corresponds to the READEXT function Immediate and asynchronous reading of n word in the extended register of a module. It is mainly used for analog input reading.
Example 1 : reading of the analog inputs on the coupler 4 (type AEM 1601/1602)
READEXT(I4,W9,W1543)
I4: address of the coupler
W9: starting address of the table
W1543 : length of the table in words
The status of each track is available in the W9 word and the measures in the following words W10 to W22
Example 2 : reading of the analog inputs on the coupler 4 (type AEM 821)
READEXT(I4,W9,W1543)
I4: address of the coupler
W9: starting address of the table
W1543 : length of the table in words
The status of each track is available in the W9 word, the status of the thresholds in the W10 word and the measures in the following words W11 to W17
Conversion to Unity-Pro :
The reconfigured ANALOG INPUTS must be copied in Unity-Pro to the images (in the example 1 to W10⇒W22)
| Function | Difficulty | Knowledge | Time |
|---|---|---|---|
| LANG | convertible | SPECI_TSX7 |