50001 - Special instructions of the TSX with parameters unsupported by the PLC Converter

Message: “At {location}, Smart instruction '{npcall}', with parameters '{param}', is not supported.”

Example: “At MAST-SR3-L:3,C:6, Smart instruction 'REXREG', with parameters '( 7, 5, 20962, 20960, 35398)', is not supported.”

Explanation: A function is used with unsupported parameters.

DMASKINT

Unmask the interruption of a coupler.

DmaskInt is not supported by PLC Converter

Function Difficulty Knowledge Time
IT non convertible SPECI_TSX7 NC

READREG

Immediate and asynchronous reading of register of a Coupler

ReadReg is not supported by PLC Converter

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

WRITEREG

Immediate and asynchronous writing of register of a Coupler

WriteReg is not supported by PLC Converter

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

READINT

Test the interruption of a coupler.

ReadInt is not supported by PLC Converter

Function Difficulty Knowledge Time
IT non convertible SPECI_TSX7 NC

ACKINT

Acknowledge the interruption of a coupler.

AckInt is not supported by PLC Converter

Function Difficulty Knowledge Time
IT non convertible SPECI_TSX7 NC

READBIT

Immediate and asynchronous reading of the value of a digital input.

This function is not supported by PLC Converter.

The code must be manually adapted taking in account that the asynchronous reading of input is not supported.

Please note that the durations of actual PLC cycle time are shorter than those of the TSX.

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

WRITEBIT

Immediate and asynchronous writing of the value of a digital output of a module. This function is not recognize by the TSX analyzer.

The code must be manually adapted taking in account that the asynchronous writing of output is not supported.

Please note that the durations of actual PLC cycle time are shorter than those of the TSX.

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

RTOR

see READBIT.

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

WTOR

see WRITEBIT.

Function Difficulty Knowledge Time
LANG non convertible SPECI_TSX7 NC

REXREG

read extended register is not supported by PLC Converter

This function corresponds to the READEXT function Immediate and asynchronous reading of n word in the extended register of a module. It is mainly used for analog input reading.

Example 1 : reading of the analog inputs on the coupler 4 (type AEM 1601/1602)

READEXT(I4,W9,W1543)

I4: address of the coupler

W9: starting address of the table

W1543 : length of the table in words

The status of each track is available in the W9 word and the measures in the following words W10 to W22

Example 2 : reading of the analog inputs on the coupler 4 (type AEM 821)

READEXT(I4,W9,W1543)

I4: address of the coupler

W9: starting address of the table

W1543 : length of the table in words

The status of each track is available in the W9 word, the status of the thresholds in the W10 word and the measures in the following words W11 to W17

Conversion to Unity-Pro :

The reconfigured ANALOG INPUTS must be copied in Unity-Pro to the images (in the example 1 to W10⇒W22)

Function Difficulty Knowledge Time
LANG convertible SPECI_TSX7