110400 - SMC Entities not translated in Unity-Pro

Message: “At {location}, SMC {entity} is not supported by Unity-Pro.”

Example: “At S89, SMC R_419 is not supported by Unity-Pro.”

Explanation:

R_416

Analog I/O card fault in module 0 in principal rack .

R_417

Analog I/O card fault in module 16 in principal rack .

R_418

Analog I/O card fault in module 32 in principal rack .

R_419

Analog I/O card fault in module 48 in principal rack .

R_420

Analog I/O card fault in module 64 in principal rack .

R_421

Analog I/O card fault in module 80 in principal rack .

R_422

Analog I/O card fault in module 96 in principal rack .

R_423

Analog I/O card fault in module 112 in principal rack .

R_424

Analog I/O card fault in module 128 in principal rack .

R_425

Fault of configuration sequence.

R_426

Fault of arithmetic unit or timestamp unit.

R_427

Fault of arithmetic unit or timestamp unit.

R_428

Fault of arithmetic unit or timestamp unit.

R_429

Fault of arithmetic unit or timestamp unit.

R_430

Fault of central unit.

R430 R431 R479 Fault
0 0 0 No fault
0 0 1 PLC in program manual mode
0 1 0 Program memory Fault
0 1 1 Watch Dog overflow
1 0 0 Battery fault on power-on
1 0 1 Program memory Fault/Battery fault
1 1 0 Battery fault/Fault of central unit and Program memory
1 1 1 Central unit Serious Fault and Program Lost

R_431

Fault of user program. see R_430.

R_432

Presence of Analog Input card on module 0 in principal rack .

R_433

Presence of Analog Input card on module 16 in principal rack .

R_434

Presence of Analog Input card on module 32 in principal rack .

R_435

Presence of Analog Input card on module 48 in principal rack .

R_436

Presence of Analog Input card on module 64 in principal rack .

R_437

Presence of Analog Input card on module 80 in principal rack .

R_438

Presence of Analog Input card on module 96 in principal rack .

R_439

Presence of Analog Input card on module 112 in principal rack .

R_440

Presence of Analog Input card on module 128 in principal rack .

R_441

R_442

Presence of arithmetic unit.

R_443

R_444

R_445

R_446

R_447

R_448

Presence of Analog Output card module 0 in principal rack .

R_449

Presence of Analog Output card module 16 in principal rack .

R_450

Presence of Analog Output card module 32 in principal rack .

R_451

Presence of Analog Output card module 48 in principal rack .

R_452

Presence of Analog Output card module 64 in principal rack .

R_453

Presence of Analog Output card module 80 in principal rack .

R_454

Presence of Analog Output card module 96 in principal rack .

R_455

Presence of Analog Output card module 112 in principal rack .

R_456

Presence of Analog Output card module 128 in principal rack .

R_468

Calcul Fault.

R_473

Overflow of immediate calcul, error immediate calcul.

R_474

Calcul Suspension (1 ⇒ Calcul suspended, 0 ⇒ Calcul executed,).

Is set to 0 at each initialisation.

R_478

RAZ calcul stack.

R_479

PLC in manual. see R_430.

R_480

Presence of Analog Input card on 1er module of an Extension Rack.

R_481

Presence of Analog Input card on 2th module of an Extension Rack.

R_482

Presence of Analog Input card on 3th module of an Extension Rack.

R_483

Presence of Analog Input card on 4th module of an Extension Rack.

R_484

Presence of Analog Input card on 5th module of an Extension Rack.

R_485

Presence of Analog Input card on 6th module of an Extension Rack.

R_486

Presence of Analog Input card on 7th module of an Extension Rack.

R_487

Presence of Analog Input card on 8th module of an Extension Rack.

R_488

Presence of Analog Input card on 9th module of an Extension Rack.

R_489

Presence of Analog Input card on 10th module of an Extension Rack.

R_490

Presence of Analog Input card on 11th module of an Extension Rack.

R_491

Fault of an Analog Input card on an Extension Rack.

R_492

Number of the faulty rack (Bit 0).

R_493

Number of the faulty rack (Bit 1).

R_494

Number of the faulty rack (Bit 2).

R_495

Number of the faulty rack (Bit 3).

R_496

Presence of Analog Output card on 1er module of an Extension Rack.

R_497

Presence of Analog Output card on 2th module of an Extension Rack.

R_498

Presence of Analog Output card on 3th module of an Extension Rack.

R_499

Presence of Analog Output card on 4th module of an Extension Rack.

R_500

Presence of Analog Output card on 5th module of an Extension Rack.

R_501

Presence of Analog Output card on 6th module of an Extension Rack.

R_502

Presence of Analog Output card on 7th module of an Extension Rack.

R_503

Presence of Analog Output card on 8th module of an Extension Rack.

R_504

Presence of Analog Output card on 9th module of an Extension Rack.

R_505

Presence of Analog Output card on 10th module of an Extension Rack.

R_506

Presence of Analog Output card on 11th module of an Extension Rack.

R_507

Analog Output card fault of an Extension Rack (Bit 0).

R_508

Analog Output card fault of an Extension Rack (Bit 1).

R_509

Analog Output card fault of an Extension Rack (Bit 2).

R_510

Reserved

C_80

Reserved

C_81

Reserved

C_82

Reserved

C_83

Reserved

C_84

Reserved

C_85

Reserved

C_86

Reserved

C_87

Reserved

C_88

Reserved

C_89

Status of the saving stack of the data memory.

C_90

Most Significant Bits : Number of actions on the Auto/Manu key. Less Significant Bits : Number of anomalies.

C_91

Reserved for calcul fault.

C_92

Hours.

C_93

Seconds.

C_94

Number of initialisations.

C_95

Rest of the division or multiplication Overflow.

M_0

Shifted Bits or error in calcul