Table of Contents
110400 - SMC Entities not translated in Unity-Pro
Message: “At {location}, SMC {entity} is not supported by Unity-Pro.”
Example: “At S89, SMC R_419 is not supported by Unity-Pro.”
Explanation:
R_416
Analog I/O card fault in module 0 in principal rack .
R_417
Analog I/O card fault in module 16 in principal rack .
R_418
Analog I/O card fault in module 32 in principal rack .
R_419
Analog I/O card fault in module 48 in principal rack .
R_420
Analog I/O card fault in module 64 in principal rack .
R_421
Analog I/O card fault in module 80 in principal rack .
R_422
Analog I/O card fault in module 96 in principal rack .
R_423
Analog I/O card fault in module 112 in principal rack .
R_424
Analog I/O card fault in module 128 in principal rack .
R_425
Fault of configuration sequence.
R_426
Fault of arithmetic unit or timestamp unit.
R_427
Fault of arithmetic unit or timestamp unit.
R_428
Fault of arithmetic unit or timestamp unit.
R_429
Fault of arithmetic unit or timestamp unit.
R_430
Fault of central unit.
| R430 | R431 | R479 | Fault |
|---|---|---|---|
| 0 | 0 | 0 | No fault |
| 0 | 0 | 1 | PLC in program manual mode |
| 0 | 1 | 0 | Program memory Fault |
| 0 | 1 | 1 | Watch Dog overflow |
| 1 | 0 | 0 | Battery fault on power-on |
| 1 | 0 | 1 | Program memory Fault/Battery fault |
| 1 | 1 | 0 | Battery fault/Fault of central unit and Program memory |
| 1 | 1 | 1 | Central unit Serious Fault and Program Lost |
R_431
Fault of user program. see R_430.
R_432
Presence of Analog Input card on module 0 in principal rack .
R_433
Presence of Analog Input card on module 16 in principal rack .
R_434
Presence of Analog Input card on module 32 in principal rack .
R_435
Presence of Analog Input card on module 48 in principal rack .
R_436
Presence of Analog Input card on module 64 in principal rack .
R_437
Presence of Analog Input card on module 80 in principal rack .
R_438
Presence of Analog Input card on module 96 in principal rack .
R_439
Presence of Analog Input card on module 112 in principal rack .
R_440
Presence of Analog Input card on module 128 in principal rack .
R_441
R_442
Presence of arithmetic unit.
R_443
R_444
R_445
R_446
R_447
R_448
Presence of Analog Output card module 0 in principal rack .
R_449
Presence of Analog Output card module 16 in principal rack .
R_450
Presence of Analog Output card module 32 in principal rack .
R_451
Presence of Analog Output card module 48 in principal rack .
R_452
Presence of Analog Output card module 64 in principal rack .
R_453
Presence of Analog Output card module 80 in principal rack .
R_454
Presence of Analog Output card module 96 in principal rack .
R_455
Presence of Analog Output card module 112 in principal rack .
R_456
Presence of Analog Output card module 128 in principal rack .
R_468
Calcul Fault.
R_473
Overflow of immediate calcul, error immediate calcul.
R_474
Calcul Suspension (1 ⇒ Calcul suspended, 0 ⇒ Calcul executed,).
Is set to 0 at each initialisation.
R_478
RAZ calcul stack.
R_479
PLC in manual. see R_430.
R_480
Presence of Analog Input card on 1er module of an Extension Rack.
R_481
Presence of Analog Input card on 2th module of an Extension Rack.
R_482
Presence of Analog Input card on 3th module of an Extension Rack.
R_483
Presence of Analog Input card on 4th module of an Extension Rack.
R_484
Presence of Analog Input card on 5th module of an Extension Rack.
R_485
Presence of Analog Input card on 6th module of an Extension Rack.
R_486
Presence of Analog Input card on 7th module of an Extension Rack.
R_487
Presence of Analog Input card on 8th module of an Extension Rack.
R_488
Presence of Analog Input card on 9th module of an Extension Rack.
R_489
Presence of Analog Input card on 10th module of an Extension Rack.
R_490
Presence of Analog Input card on 11th module of an Extension Rack.
R_491
Fault of an Analog Input card on an Extension Rack.
R_492
Number of the faulty rack (Bit 0).
R_493
Number of the faulty rack (Bit 1).
R_494
Number of the faulty rack (Bit 2).
R_495
Number of the faulty rack (Bit 3).
R_496
Presence of Analog Output card on 1er module of an Extension Rack.
R_497
Presence of Analog Output card on 2th module of an Extension Rack.
R_498
Presence of Analog Output card on 3th module of an Extension Rack.
R_499
Presence of Analog Output card on 4th module of an Extension Rack.
R_500
Presence of Analog Output card on 5th module of an Extension Rack.
R_501
Presence of Analog Output card on 6th module of an Extension Rack.
R_502
Presence of Analog Output card on 7th module of an Extension Rack.
R_503
Presence of Analog Output card on 8th module of an Extension Rack.
R_504
Presence of Analog Output card on 9th module of an Extension Rack.
R_505
Presence of Analog Output card on 10th module of an Extension Rack.
R_506
Presence of Analog Output card on 11th module of an Extension Rack.
R_507
Analog Output card fault of an Extension Rack (Bit 0).
R_508
Analog Output card fault of an Extension Rack (Bit 1).
R_509
Analog Output card fault of an Extension Rack (Bit 2).
R_510
Reserved
C_80
Reserved
C_81
Reserved
C_82
Reserved
C_83
Reserved
C_84
Reserved
C_85
Reserved
C_86
Reserved
C_87
Reserved
C_88
Reserved
C_89
Status of the saving stack of the data memory.
C_90
Most Significant Bits : Number of actions on the Auto/Manu key. Less Significant Bits : Number of anomalies.
C_91
Reserved for calcul fault.
C_92
Hours.
C_93
Seconds.
C_94
Number of initialisations.
C_95
Rest of the division or multiplication Overflow.
M_0
Shifted Bits or error in calcul