General informations for conversions

The conversion tools for PLC code allow important productivity gains. But they do not replace the expertise of an automatician. Then, except for some of them, the special functions, the communications, the regulations, the axes and motions, etc… are not translated. Furthermore in all case a complete rereading of the code is necessary before the restart of the application.

see:

Checklist to do a conversion

  1. export the source files from the old PLC workbench. (see how to export sources files)
  2. use the PLC Converter to convert the application and obtain the result files and report
  3. see result report details:
    • each message generated in the report is associated to a severity (error, warning or info).
    • example of message : “Error: TSX sw55 is not supported by Unity-Pro. Please review the destination file.”
    • Some kind of messages are associated to a link to the knowledge base
    1. check if some specific messages ask to modify the result file before importing it into the destination PLC workbench. If so deals with the required modifications.
  4. Import the result file into the destination PLC workbench (ex: UnityPro)
  5. The first verification to be done is after the import:
    1. Do the correction of the import error generated by the destination PLC workbench
    2. Launch the analyze of application on the destination PLC workbench
    3. Do the correction of the analyze generated by the destination PLC workbench
  6. The second verification is to use the result report details to check each message in order to localize :
    • the untranslated system bits/words
    • the untranslated functions
    • the unsupported architecture/types,
    • …
    1. more details can be found in the report in the conversion path appendix.
  7. Finally, a complete review of the application must be done before the commissioning. This last step is fundamental and should not be neglected.