The PL7-3 range PLC models belong to many versions that correspond to the different PLC upgrades. A given version of a PLC can only execute an application code of the same version. In other terms the binary file containing the code is not compatible between versions. Whereas it is possible to migrate the programs to later versions.
The converter takes in charge the programs generated under versions 4 or later
From the version 4, the TSX UCs and the PMX UCs are the two types PLC CPUs. The PMX UCs allow the use of control and regulation function blocks. The different PLCs are :
The converter supports files from the X-TEL workbench for versions 4 and later.
Under a previous version, use the X-TEL workbench to internal conversion to version 4. Then the binary obtained is analyzable by the converter.
Get files from a XTEL Application:
In the first case, just follow the instructions to recover data files in the TSX Source files section. In the second case, it is necessary previously to retrieve the contents of the archive. MS-DOS archives consist of CONTROL and BACKUP files numbered according to the size of the archive. For example, the following files are an archive into a minimum of three disks:
Normally the RESTORE tool is capable of reproducing the contents of the archive. However versions RESTORE depend on the version of MS-DOS and are mutually incompatible. In case you would not succeed in extracting their contents, contact Itris Automation Square.
The optimal translation uses all of the following files:
The name of the BIN file can sometimes be a problem. The *. BIN can not have the same name as TSX task. Then just rename it before sending it to us.
For now the TSX parsed languages are :
The binary code includes both graphic representations and assembler of the PLC code. The TSX parser uses the assembler code to generate the Glips file.
Contact order may be changed between Tsx ladder and generated ladder
In ladder, behavior is the same even if a variable was read and write in the same rung. This is done by creating a temporary variable to reproduce TSX Ladder evaluation order.
The PL7-3 analyzer knows :
The following variables are considered as outputs :
For now there is no support for FIPIO. You will find some 'unknown_word' and 'rioxxxx' variables within the code. The FIPIO bits are recognized but not decoded. The FIPIO words are neither recognized nor decoded.
A FAIRE: The conversion must be manually realized for all the equations and sequencies containing FIPIO variables.
For now there is no support for the OFBs OFB, family, class and instance decoding is not supported. Access to variables included in OFBs are performed properly, nor OFB calls.
TO DO: - list every used OFB and its configuration in the source program. - select the corresponding function block in the destination architecture and adjust the settings.
READBIT, WRITEBIT, READREG, WRITEREG, MASKINT, DMASKINT, READINT, ACKINT, READEXT are not supported. An exception is generated within the code, located at the line where the function is called.
The binary files older than version 4 is not possible for now. It is necessary to convert from version 3 to version 4 using XTel workshop and then export version 4.