Message: “ RSLogix5000 {entity} is not supported by Unity-Pro.”

Example: “ RSLogix5000 MSG is not supported by Unity-Pro.”

Explanation:

MSG

Warning: the MSG function must be redefined by using the corresponding communication function in PLC destination library.

Function Difficulty Knowledge Time
COM convertible GENE_API 5 Min

SSV

Allows to set the system variables. Some attributs (LASTSCANTIME, MAXSCANTIME, etc.) of this function may be translated manually in Unity-Pro by using the correspondings system words.

Function Difficulty Knowledge Time
SYSTEM convertible GENE_API X Min

GSV

Allows to get the system variables. Some attributs (LASTSCANTIME, MAXSCANTIME, etc.) of this function may be translated manually in Unity-Pro by using the correspondings system words.

Function Difficulty Knowledge Time
SYSTEM convertible GENE_API X Min

IOT

Immediate update of outputs is not available in the Unity-Pro premium library. Nevertheless, a restrictive version of this function exist in the Unity-Pro quantum library (IMIO_OUT). Please review the destination file.

Function Difficulty Knowledge Time
IO convertible EXPERT X Min

ABL

ASCII Test For Buffer Line.

Determine when the buffer contains termination characters.

Please review the destination file.

Function Difficulty Knowledge Time
COM convertible EXPERT X Min

ACB

ASCII Chars in Buffer.

Count the characters in the buffer.

Please review the destination file.

Function Difficulty Knowledge Time
COM convertible EXPERT X Min

ACL

ASCII Clear Buffer.

Clear the buffer or Clear out ASCII Serial Port instructions that are currently executing or are in the queue.

Please review the destination file.

Function Difficulty Knowledge Time
COM convertible EXPERT X Min

AHL

ASCII Set/Reset Handshake Lines.

Obtain the status of the serial port control lines or Turn on or off the DTR signal or Turn on or off the RTS signal.

Please review the destination file.

Function Difficulty Knowledge Time
COM convertible EXPERT X Min

ARD

ASCII Read.

Read a fixed number of characters.

Please replace this function by the INPUT_CHAR or OUT_IN_CHAR function of the Unity-Pro library.<br/>

The important parameters to know for translation to Unity-Pro are:

ARD parameters INPUT_CHAR parametersInformations
DestinationRECPReceived string
Serial Port Control lengthNBNumber of caracters to receive
Function Difficulty Knowledge Time
COM convertible EXPERT X Min

ARL

ASCII Read Line

Read a varying number of characters, up to and including the first set of termination characters.

Please replace this function by the INPUT_CHAR function or OUT_IN_CHAR of the library Unity-Pro.<br/>

The important parameters to know for translation to Unity-Pro are:

ARL parameters INPUT_CHAR parametersInformations
DestinationRECPReceived string
Serial Port Control lengthNBNumber of caracters to receive
Function Difficulty Knowledge Time
COM convertible EXPERT X Min

AWA

ASCII Write Apend.

Send characters and automatically append one or two additional characters to mark the end of the data.

Please replace this function by the PRINT_CHAR or OUT_IN_CHAR function of the Unity-Pro library.

The important parameters to know for translation to Unity-Pro are:

AWA parameters PRINT_CHAR parametersInformations
SourceEMISstring to be emitted
Serial Port Control lengthGEST[4]Number of characters to be emitted

NOTA: the choice of the additional characters to mark the end of the data is made in the configuration of the communication card.

Function Difficulty Knowledge Time
COM convertible EXPERT X Min

AWT

ASCII Write.

Send characters.

Please replace this function by the PRINT_CHAR function or OUT_IN_CHAR of the Unity-Pro library.

The important parameters to know for translation to Unity-Pro are:

parameters AWT parameters PRINT_CHARInformations
SourceEMISstring to be emitted
Serial Port Control lengthGEST[4]Number of characters to be emitted
Function Difficulty Knowledge Time
COM convertible EXPERT X Min