Table of Contents

110000 - System Bits and words or PL7-3 serie 7 object unsupported by Unity-Pro

Message: “ TSX {entity} is not supported by Unity-Pro. Please review the destination file.”

Example: “ TSX sw55 is not supported by Unity-Pro. Please review the destination file.”

Explanation: It is mainly caused by unsupported system bits and words from TSX.

sy2

Immediate Restart.

Function Difficulty Competence Duration
system SPECI_TSX7 ,

sy3

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy8

Security of in rack outputs. Normally set to 1.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy11

Refreshing of common words. Normally set to 0, it is set to 1 as soon as a station has emit its common variable on the network. It can be set to 0 by program or terminal.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy12

network 1 operational. Normally set to 0, it is set to 1 as soon as the coupler is operational.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy13

network 2 in operation. idem SY12

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy14

network 3 in operation. idem SY12

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy15

network 4 in operation. idem SY12

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy25

Multi-activity of a macro-step. Normally set to 0, it is set to 1 when more than one steps are active in a macro with a OR divergence.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy26

Activation overflow Normally set to 0, it is set to 1 when there is an overflow of the activation possibility (step and transitions). For Unity-Pro it is possible to activate 100 steps by SFC section.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy27

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy32

Security of the in rack outputs. the behavior is identical for the SY32 to SY39 bits. Normally set to 1, they may be set to 0 by program or terminal. They are affected to the slot (aux bacs) of the cards of outputs.

Bacs0/12/34/56/78/9A/BC/DE/F
BitsSY32SY33SY34SY35SY36SY37SY38SY39

In case of abnormal execution of the program, if SY8=1, then the outputs associated to the System bit are forced to 0 bythe TSX system.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy33

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy34

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy35

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy36

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy37

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy38

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy39

Security of the in rack outputs. Idem Sy32.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy48

Validation of the execution duration or max duration of the periodic tasks. Normally set to 0.

For Unity-Pro

Main task FAST Task Aux0 task Aux1 task Aux2 task Aux3 task
Dur last cycleSW30SW33SW36SW39SW42SW45
Dur cycle maxSW31SW34SW37SW40SW43SW46
Dur last minSW32SW35SW38SW41SW44SW47
Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy49

SY49 and SY50 : Management of the time. Normally set to 0

SY49=0SY49=1
SY50=0Reading date and time in the SW50-SW57Access to the date, time and code of the last stop
SY50=1Writing date and time in the SW50-SW57
Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy51

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy52

RAZ messages counters. No documentation on version PL7-3 V5.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy84

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy96

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy108

UNI-TELWAY option integrated. No documentation on version PL7-3 V5.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy116

Suspension of the control of the in rack outputs Normally set to 0, this bit stops the update of the analog and digital outputs. (Freeze the outputs).

For Unity-Pro : %SW9 : Allows to inhibit the update of the outputs of each task.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy117

Suspension of the acquisition of the inputs in rack Normally set to 0, this bit stops the acquisition of the analog and digital inputs. For Unity-Pro : %SW8 : Allows to inhibit the acquisition of the inputs of each task :

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy120

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy121

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sy126

System bit reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw0

Update of the common words of the primary network.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw1

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw3

Table of the 16 stations of the primary network. This word indicates the status of the 16 first stations. The status 1 ⇒ Station in operation (TELWAY)

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw4

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw5

Time of immediate restart.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw6

Table of activity of the SFC steps.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw7

Table of validity of the SFC transitions.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw8

SW8-SW11 : Reset of the SFC macro-steps. Each bit of those words correspond to one of the 64 macro-steps.

For Unity-Pro : See the function “INITCHART”.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw9

SW8-SW11 : Reset of the SFC macro-steps. See SW8.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw10

SW8-SW11 : Reset of the SFC macro-steps. See SW8.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw11

SW8-SW11 : Reset of the SFC macro-steps. See SW8.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw12

SW12-SW15 : Table of survey of the SFC macro-steps. Each bit of those words correspond to one of the 64 macro-steps.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw13

SW12-SW15 : Reset of the SFC macro-steps. See SW12.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw14

SW12-SW15 : Reset of the SFC macro-steps. See SW12.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw15

SW12-SW15 : Reset of the SFC macro-steps. See SW12.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw16

%SW16-%SW18 : Copy part of the RAM-SYSTEM.

For Unity-Pro : Use the function READ_PCMCIA(Slot_Number, Source_Address, Words_Number, Dest_Address, Read_State);

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw17

%SW16-%SW18 : Copy part of the RAM-SYSTEM. See %SW16

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw18

%SW16-%SW18 : Copy part of the RAM-SYSTEM. See %SW16

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw19

Modification of the period of the tasks.

xxxx TASK N° Period

PERIOD :

TASK N° :

For Unity-Pro :

%SW0Modification of MAST task period1-255 ms (0: Cyclic)
%SW1Modification of FAST task period1-255 ms
%SW2-%SW5Modification of Auxiliary tasks period10ms-2,55s ( in x10ms)
Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw20

%SW20-%SW21 : System operation duration. Those words contain the elapsed time since the last cold restart. In x100ms.

For Unity-Pro : Replace by %SW18 and %SW19.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw21

%SW20-%SW21 : System operation duration. %SW20

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw22

%SW22-%SW23 : Application operation duration. Idem %SW20 but reset the counter on SY1.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw23

%SW22-%SW23 : Application operation duration.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw24

No documentation on PL7-3 V5

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw46

Maximal execution duration of the interruption task.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw47

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw48

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw50

sw50: the SW50 to SW57 system words are relatives to the management of the time. They contain depending on the state of the bits sy49 and sy50 either

words Signification
SW50 word always set to 0
SW51 seconds (0..59)
SW52 minutes (0..59)
SW53 hours (0..23)
SW54 days (1..31)
SW55 mois (1..12)
SW56 years (0..9999)
SW57 day of the week (0..6) or stop code if reading last execution stop
Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw51

sw51 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw52

sw52 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw53

sw53 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw54

sw54 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw55

sw55 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw56

sw56 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw57

sw57 : This System word is part of the management of the time (refer to SW50 for the explanation of the system words relative to the management of the time).

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw58

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw60

Fatal Error Code. System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw61

%SW61-%SW63 : Unknown NPCALL code. System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw62

%SW61-%SW63 : Unknown NPCALL code. See SW60

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw63

%SW61-%SW63 : Unknown NPCALL code. See SW60

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw64

%SW64-%SW67 : information word on refreshment of the common words of the 1st coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw65

%SW64-%SW67 : information word on refreshment of the common words of the 1st coupler. See SW64

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw66

%SW64-%SW67 : information word on refreshment of the common words of the 1st coupler. See SW64

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw67

%SW64-%SW67 : information word on refreshment of the common words of the 1st coupler. See SW64

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw68

%SW68-%SW71 : information word on status coupler of the 1st coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw69

%SW68-%SW71 : information word on status coupler of the 1st coupler.SW68

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw70

%SW68-%SW71 : information word on status coupler of the 1st coupler.SW68

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw71

%SW68-%SW71 : information word on status coupler of the 1st coupler.SW68

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw72

Network address of the first coupler

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw73

%SW73-%SW76 : information word on refreshment of the common words of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw74

%SW73-%SW76 : information word on refreshment of the common words of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw75

%SW73-%SW76 : information word on refreshment of the common words of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw76

%SW73-%SW76 : information word on refreshment of the common words of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw77

%SW77-%SW80 : information word on status coupler of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw78

%SW77-%SW80 : information word on status coupler of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw79

%SW77-%SW80 : information word on status coupler of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw80

%SW77-%SW80 : information word on status coupler of the 2nd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw81

Network address of the second coupler

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw82

%SW82-%SW85 : information word on refreshment of the common words of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw83

%SW82-%SW85 : information word on refreshment of the common words of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw84

%SW82-%SW85 : information word on refreshment of the common words of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw85

%SW82-%SW85 : information word on refreshment of the common words of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw86

%SW86-%SW89 : information word on status coupler of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw87

%SW86-%SW89 : information word on status coupler of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw88

%SW86-%SW89 : information word on status coupler of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw89

%SW86-%SW89 : information word on status coupler of the 3rd Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw90

Network address of the third coupler

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw91

%SW91-%SW94 : information word on refreshment of the common words of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw92

%SW91-%SW94 : information word on refreshment of the common words of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw93

%SW91-%SW94 : information word on refreshment of the common words of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw94

%SW91-%SW94 : information word on refreshment of the common words of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw95

%SW95-%SW98 : information word on status coupler of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw96

%SW95-%SW98 : information word on status coupler of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw97

%SW95-%SW98 : information word on status coupler of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw98

%SW95-%SW98 : information word on status coupler of the 4th Coupler.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw99

Network address of the fourth coupler

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw100

SW100-SW115 : Register for UNI-TELWAY integrated socket SW100 : word status

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw101

SW100-SW115 : Register for UNI-TELWAY integrated socket SW101-SW102 : word of status of the data events

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw102

SW100-SW115 : Register for UNI-TELWAY integrated socket SW101-SW102 : word of status of the data events

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw108

SW100-SW115 : Register for UNI-TELWAY integrated socket SW108 : word of control

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw117

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw118

%SW118-%SW121 :Remote I/O fault. Each bit in this group of words represents the status of a connection point. The presence of a bit at 0 indicates the appearance of an exchange fault or a fault in the discrete process with the equipment : SW118,0 = equipment at connection point 0, etc.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw119

%SW118-%SW121 :Remote I/O fault. Each bit in this group of words represents the status of a connection point. The presence of a bit at 0 indicates the appearance of an exchange fault or a fault in the discrete process with the equipment : SW118,0 = equipment at connection point 0, etc.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw120

%SW118-%SW121 :Remote I/O fault. Each bit in this group of words represents the status of a connection point. The presence of a bit at 0 indicates the appearance of an exchange fault or a fault in the discrete process with the equipment : SW118,0 = equipment at connection point 0, etc.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw121

%SW118-%SW121 :Remote I/O fault. Each bit in this group of words represents the status of a connection point. The presence of a bit at 0 indicates the appearance of an exchange fault or a fault in the discrete process with the equipment : SW118,0 = equipment at connection point 0, etc.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

sw122

System word reserved on PL7-3 V5. No documentation.

Function Difficulty Knowledge Duration
system SPECI_TSX7 ,

dtf

Transcoding BCD to float

Function Difficulty Knowledge Duration
PROG not easy SPECI_TSX7

t_ctrl1

start stop of the IT task

Function Difficulty Knowledge Duration
IT non convertible SPECI_TSX7

txt

TXT blocs for local/network configuration and communication

Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7 ,

txtsys

System TXT bloc for local/network configuration and communication

Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7 ,

txtter

terminal bloc text local/network

Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7 ,

txtcpl

coupler TXT bloc local/network

Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7 ,

txttlg

TLG TXT bloc only network

Function Difficulty Knowledge Duration
TXT non convertible SPECI_TSX7

reset

Cancel the exchange of TXT bloc

Using this RESET instruction will:

  1. prevents the execution of INPUT, OUTPUT and EXCHG instructions,
  2. stops the ongoing exchange
  3. set to 1 the TXTi,D (exchange terminated) and TXTi,E (wrong exchange) output bits.

The TXTi,S status word contain then the error code.

Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7

exchg

transmission / reception of a TXT bloc

This EXCHG instruction:

  1. sends the transmission table
  2. and then sets the TXT bloc in reception mode to allow to store a message in the reception table, if the TXTi,D bit is equal to 1.
Function Difficulty Knowledge Duration
TXT convertible SPECI_TSX7

slcword

shift of 1 byte to the right.

It is mainly used for communication or regulation. In those cases it can be removed from the destination file. Please review the destination file.

Function Difficulty Knowledge Time
PROG convertible GENE_API ,