====== 50001 - Special instructions of the TSX with parameters unsupported by the PLC Converter ====== Message: "At {location}, Smart instruction '{npcall}', with parameters '{param}', is not supported." Example: "At MAST-SR3-L:3,C:6, Smart instruction 'REXREG', with parameters '( 7, 5, 20962, 20960, 35398)', is not supported." Explanation: A function is used with unsupported parameters. ===== DMASKINT ===== Unmask the interruption of a coupler. DmaskInt is not supported by PLC Converter ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | IT | non convertible | SPECI_TSX7 | NC | ===== READREG ===== Immediate and asynchronous reading of register of a Coupler ReadReg is not supported by PLC Converter ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== WRITEREG ===== Immediate and asynchronous writing of register of a Coupler WriteReg is not supported by PLC Converter ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== READINT ===== Test the interruption of a coupler. ReadInt is not supported by PLC Converter ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | IT | non convertible | SPECI_TSX7 | NC | ===== ACKINT ===== Acknowledge the interruption of a coupler. AckInt is not supported by PLC Converter ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | IT | non convertible | SPECI_TSX7 | NC | ===== READBIT ===== Immediate and asynchronous reading of the value of a digital input. This function is not supported by PLC Converter. The code must be manually adapted taking in account that the asynchronous reading of input is not supported. Please note that the durations of actual PLC cycle time are shorter than those of the TSX. ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== WRITEBIT ===== Immediate and asynchronous writing of the value of a digital output of a module. This function is not recognize by the TSX analyzer. The code must be manually adapted taking in account that the asynchronous writing of output is not supported. Please note that the durations of actual PLC cycle time are shorter than those of the TSX. ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== RTOR ===== see [[#readbit|READBIT]]. ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== WTOR ===== see [[#writebit|WRITEBIT]]. ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | non convertible | SPECI_TSX7 | NC | ===== REXREG ===== read extended register is not supported by PLC Converter This function corresponds to the **READEXT** function Immediate and asynchronous reading of n word in the extended register of a module. It is mainly used for analog input reading. **Example 1** : reading of the analog inputs on the coupler 4 (type **AEM 1601/1602**) READEXT(I4,W9,W1543) I4: address of the coupler W9: starting address of the table W1543 : length of the table in words The status of each track is available in the W9 word and the measures in the following words **W10 to W22** **Example 2** : reading of the analog inputs on the coupler 4 (type **AEM 821**) READEXT(I4,W9,W1543) I4: address of the coupler W9: starting address of the table W1543 : length of the table in words The status of each track is available in the W9 word, the status of the thresholds in the W10 word and the measures in the following words **W11 to W17** **Conversion to Unity-Pro :** The reconfigured ANALOG INPUTS must be copied in Unity-Pro to the images (in the example 1 to W10=>W22) ^ Function ^ Difficulty ^ Knowledge ^ Time ^ | LANG | convertible | SPECI_TSX7 | |